17. Binary Values (BV)

Obj ID

Obj Name

Read/ Write

Inactive (OFF) Text

Active (ON) Text

BV1

Run FWD Cmd

Write

OFF

RUN FWD

BV2

Run REV Cmd

Write

OFF

RUN REV

BV3

Ext Fault Cmd

Write

OFF

EXT FAULT

BV4

Fault Reset Cmd

Write

OFF

RESET

BV5

Com Net Cmd

Write

LOCAL

COM

BV6

Com Cntrl Cmd

Write

LOCAL

COM

BV7

MF Input 3 Cmd

Write

OFF

ON

BV8

MF Input 4 Cmd

Write

OFF

ON

BV9

MF Input 5 Cmd

Write

OFF

ON

BV10

MF Input 6 Cmd

Write

OFF

ON

BV11

MF Input 7 Cmd

Write

OFF

ON

BV12

Set Fault Contact Cmd

Write

OFF

ON

BV13

RUN-STOP

Read

OFF

RUN

BV14

REV-FWD

Read

FWD

REV

BV15

READY

Read

OFF

READY

BV16

FAULT

Read

OFF

FAULTED

BV17

Data Set Error

Read

OFF

ERR

BV18

Overcurrent – Ground Fault

Read

OFF

OC - GF

BV19

Main Circuit – Overvoltage

Read

OFF

OV

BV20

Drive Overload

Read

OFF

OL2

BV21

Drive Overheat

Read

OFF

OH1 – OH2

BV22

Fuse Blown

Read

OFF

PUF

BV23

PI Feedback Loss

Read

OFF

FBL

BV24

External Fault

Read

OFF

E0 - EF

BV25

Hardware Error

Read

OFF

CPF

BV26

Motor Overload - Overtorque

Read

OFF

OL1 – OL3

BV27

Overspeed

Read

OFF

OS – DEV

BV28

Main Circuit Under Voltage

Read

OFF

UV

BV29

MCU, Control Power Supply Error

Read

OFF

UV1 – 2 – 3

BV30

In/Out Phase Loss

Read

OFF

LF

BV31

Communication Error

Read

OFF

CE

BV32

Operator Disconnect

Read

OFF

OPR

BV33

Operating

Read

OFF

ON

BV34

Zero Speed

Read

OFF

ON

BV35

Frequency Agree

Read

OFF

ON

BV36

Desired Frequency Agree

Read

OFF

ON

BV37

Frequency Detect 1

Read

OFF

ON

BV38

Frequency Detect 2

Read

OFF

ON

BV39

Drive Startup Complete

Read

OFF

ON

BV40

Low Voltage Detect

Read

OFF

ON

BV41

Base Block

Read

OFF

ON

BV42

Frequency Ref Mode

Read

COM

LOCAL

BV43

Run Command Mode

Read

COM

LOCAL

BV44

Overtorque Detect

Read

OFF

ON

BV45

Frequency Reference Loss

Read

OFF

ON

BV46

Retry Error

Read

OFF

ON

BV47

Modbus Comms Error

Read

OFF

ON

BV48

Modbus Timeout Error

Read

OFF

ON

BV49

Crc Error

Read

OFF

ON

BV50

Invalid Data Length

Read

OFF

ON