Date: 7/07/2011 Rev: 11-07

BACnet

®

Option

Installation Guide

1. BACnet network address set by dip switches A0-A5
on option card.

10. Set the Device Instance ID

The CM049 option arrives from the factory with the Device Instance
Identifier set to 0.
To change it, send a WriteProperty, objectidentifier = device, ID, where ID is
a number between 1 and 4194302, inclusive. The message DADR is the
CM049 address as represented by the dip switches on the CM049 option.

11. LED Status Indicators and Diagnostics

H5-08

Protocol Select

0

MODBUS (BACnet)

0

1

N2 (Metasys)

2

P1 (APOGEE)

H5-09

CE Detect Time

0.0 sec ~ 10.0 sec

2.0 sec

Parameter

Function

Data

Description

Default

LED Display

Condition

PWR

RX

TX

OFF

OFF

OFF

No Power to Option

ON

Option Powered

ON

OFF

ON

BACnet network disconnected. The transmit LED will flash for a short while after the
network has been disconnected.

ON

OFF

OFF

BACnet network disconnected

ON

ON

BACnet Receive Message

Due to the speed of the BACnet
communication, these LEDs should flash
at an extremely fast rate.

ON

ON

BACnet Send Message

Operator displays EF0

Either the BACnet cable is disconnected
or the BACnet card cannot communicate
with the drive.

ACT

ERR

Condition

OFF

OFF

Option not communicating with drive. Check S+/S- and R+/R- connections.

GREEN

OFF

Communicating with the drive over RS485

RED

An error has occurred in communicating with the drive

RED

Operator displays EF0

The BACnet card cannot communicate with
the drive.

Operator displays CE

The drive cannot communicate with the
BACnet card.