Bacnet, Option installation guide – Yaskawa BACnet Option User Manual
Page 7

Yaskawa America, Inc. –
IG.AFD.23.BACnet, Page 7 of 12
Date: 7/07/2011 Rev: 11-07
BACnet
®
Option
Installation Guide
16. Analog Values (AV)
Obj ID
Obj Name
Bit
Name
Read/ Write
Scale
Unit
AV1
Operation Cmd
0
Run Forward
Write
Bit Field
1
Run Reverse
2
External Fault (EF0)
3
Fault Reset
4
ComNet
5
ComRef
6
Multi-Function Input 3
7
Multi-Function Input 4
8
Multi-Function Input 5
9
Multi-Function Input 6
10
Multi-Function Input 7
11
Multi-Function Input 8
12
Reserved
13
Reserved
14
Reserved
15
Reserved
AV2
Frequency Cmd
Scaled by o1-03 with Units selected by Parameter o1-09
Write
o1-03
o1-09
AV3
1
PI Setpoint Cmd
Reference Select PID (BO4) must be set to ON in order to use AV3
Scaled by Parameter b5-20 with Units by b5-31
Write
b5-20
b5-31
AV4
MF Outputs Cmd
0
Relay Output
Write
1
PCH1
2
PCH2
3
Reserved
4
Reserved
5
Reserved
6
Error Relay Enable (Must be Set Before bit 7)
7
Error Relay
8-15
Reserved
AV5
Reference Select
Cmd
0
Reserved
Write
Bit Field
1
Ref. Select PID
2-11
Reserved
12
Ref. Select Terminal 5
13
Ref. Select Terminal 6
AV6
Drive Status
0
@ Run
Read
Bit Field
1
@ Reverse
2
@ Inverter Ready
3
@ Fault
4
@ Data Set Error
5
@ Relay Output
6
@ PCH1
7
@ PCH2
8-15
Reserved
Note
1
In order to use AV3
(Ref Sel: PI Setpoint)
Set b5-01 = 1
Set BO4 (Ref Sel: PI Setpoint) to ON
Set the desired value in AV3 in percent of max frequency