6 Related Drive Parameters

YASKAWA ELECTRIC TOBP C730600 62B 1000-Series Option SI-ET3 Installation Manual

27

F6-08
(36A)

Reset Communication
Related Parameters

Determines if communication-related parameters F6-††
and F7-†† are set back to original default values when
the drive is initialized using parameter A1-03.
0: Do not reset parameters
1: Reset parameters

Default: 0
Range: 0, 1

F6-20

<5> <6>

MECHATROLINK
Station Address

Sets the station number.

Default: 21H
Range: 20 to 3FH

F6-21

<5>

MECHATROLINK
Frame Size

Sets the frame size.
0: 64 byte
1: 32 byte

Default: 0
Range: 0, 1

F6-23

<5> <7>

MECHATROLINK
Monitor Selection
(Code 0EH)

Set MEMOBUS/Modbus register to monitor SEL_MON
of INV_CTL and INV_CTL.

Default: 0H
Range: 0 to
FFFFH

F6-24

<5> <8>

MECHATROLINK
Monitor Selection
(Code 0FH)

Set MEMOBUS/Modbus register to monitor SEL_MON
of INV_CTL and INV_CTL.

Default: 0H
Range: 0 to
FFFFH

F6-25

Operation Selection at
Watchdog Error (E5)

0: Ramp to stop. Decelerate to stop using the deceleration
time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration
time in C1-09.
3: Alarm only.

Default: 1
Range: 0 to 3

F6-26

MECHATROLINK bUS
Errors Detected

Sets the number of option communication errors (bUS).

Default: 2
Range: 2 to 10

<1> To start and stop the drive with the MECHATROLINK-III master device using serial communications, set b1-02

to 3. To control the frequency reference of the drive via the master device, set b1-01 to 3.

<2> If set to 3, then the drive will continue to operate when a fault is detected. Take proper measures such as installing

an emergency stop switch.

<3> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines

whether the value is read as the Torque Limit value (d5-01 = 0) or read as the Torque Reference value (d5-01 = 1).

In CLV/PM, this value is read as the Torque Limit.

<4> The setting specifies that the Torque Reference or Torque Limit is to be provided via network communications

(F6-06 = 1). The motor may rotate if no torque reference or Torque Limit is supplied from the PLC.

<5> Power must be cycled in order for any setting changes to take affect.

<6> All station addresses must be unique. If set to 20 or 3F, a Station Address Error (AEr) will occur and the ERR light

will turn on.

<7> Setting byte 10 of INV_CTL to 0EH enables the register set by F6-23. Byte 11 and 12 of the response data enable

the register content set by F6-23. Refer to the drive instruction manual for details on the register that can be set.

<8> Setting byte 10 of INV_CTL to 0FH enables the register set by F6-24. Byte 11 and 12 of the response data enable

the register content set by F6-24. Refer to the drive instruction manual for details on the register that can be set.

No.

(Addr.

Hex)

Name

Description

Values