Message

Cause and corrective measure

Iac-DC_Offs-Srr
Iac-DC_Offs-Bfr

Excessive DC current has been detected during feed-in operation.
Corrective measures:

• Ensure that the grid conditions are complied with.
• If this message is displayed frequently or recurrently, contact

the SMA Service Line.

Imax

Overcurrent on the AC side. The current at the AC terminal is higher
than specified.
Corrective measures:

• Ensure that the PV system is designed correctly.
• Ensure that the grid conditions are complied with.

K1-Close
K1-Open
K2-Open

Fault during relay test.
Corrective measures:

• If this disturbance occurs frequently or several times

consecutively, contact the SMA Service Line.

MSD-dI
MSD‑Fac
MSD-Vac
MSD-Timeout

Internal measurement comparison fault or the hardware is defective.
Corrective measures:

• If this message is displayed frequently, contact the

SMA Service Line.

Offset

Disturbance in recording measured values.
Corrective measures:

• If this message is displayed frequently, contact the

SMA Service Line.

Earthfault

The electrical insulation between the PV system and ground is defec-
tive. The resistance between the positive and negative DC terminal
to ground is outside the permissible range.
Corrective measures:

• Ensure that the PV system is insulated correctly.
• Check the PV array for ground faults (see Section 4.2.2, page 16

).

ROM

The inverter firmware is faulty.
Corrective measures:

• If this message is displayed frequently, contact the

SMA Service Line.

Shutdown

Temporary inverter disturbance.
Corrective measures:

• Contact the SMA Service Line.

4 Troubleshooting