6  Electrical connection

Installation Guide

DISU_SCUS-IA-IUS111711

57

6.6 Closing the Disconnect Unit

☐ The handles on the front plate of the enclosure must be set to ”Off”, so that the shafts can snap

in.

☐ The 2 mounting clamps for the front plate of the enclosure must be set to the correct position

(see figure below). The 2 mounting clamps are moveable and must be arranged
11

3

4

 in. … 1 ft. 3

3

4

 in. (300 mm … 400 mm) from the sides.

Figure 44: Position of the mounting clamps.

2. Connect the ground strap from the bottom left

corner of the Disconnect Unit to the front plate of
the enclosure. Fasten the screw with a torque of
70 in‒lb. (8 Nm).

1.

$"65*0/

Danger of crushing
Take into account the heavy weight of the front plate of the enclosure.

• Two persons are needed to move the front plate of the enclosure to the Disconnect Unit.
• Make sure that one person always holds the front plate of the enclosure while the other

person performs work at it.

• Hold the front plate of the enclosure with 2 hands and move it to the front of the

Disconnect Unit. The distance between the Disconnect Unit and its front plate must be
approximately 8 in. (200 mm).

DISCO

NNEC

T UNIT

SMA