beautypg.com

5 connecting ac cables to busbars, Connecting ac cables to busbars – SMA SC 250U User Manual

Page 51

background image

SMA America, LLC

6  Electrical connection

Installation Guide

DISU_SCUS-IA-IUS111711

51

6.4.5 Connecting AC cables to busbars

%"/(&3

High voltages are present in the live components of the low voltage grid.
Death resulting from burning and electric shock.

• Pay close attention to all safety precaution measures regarding the low-voltage grid.
• Switch off the AC and DC circuit breaker/load break switches and secure it against accidental

switching on.

• Ensure that no voltage is present.

$"65*0/

Danger of fire caused by wrong arrangement of AC cables.
Wrong arrangement of AC cables can result overheating of the cables and causes the danger of
fire.

• Arrange the cables as described in 6.4.2 ”Arranging AC cables”, page 41.

$"65*0/

Danger of fire caused by improper connection to the power distribution grid.

• To reduce the risk of fire, do not connect to an AC load center (circuit breaker panel) having

multi-wire branch circuits connected.

This manual is related to the following products: