beautypg.com

Procedure of connecting – SMA SC 250U User Manual

Page 39

background image

SMA America, LLC

6  Electrical connection

Installation Guide

DISU_SCUS-IA-IUS111711

39

Figure 19: Mounted cable lugs

Procedure of connecting

2. Position the cable lug or lugs on the busbar.
3. Tighten the screw with a nut in a clockwise direction. For torques refer to the table (see section

6.2 ”Cable requirements”, page 32).

4. Connect all DC cables as illustrated above.

1.

/05*$&

Oxide layers on contact surfaces after transport and storing of the Disconnect Unit.
Yield loss resulting due to poor electrical conductivity.

• Before connecting the cables, clean the contact surfaces.
• Use only the non-woven abrasive delivered with the Sunny Central.
• Do not clean the surfaces with sandpaper.
• Do not damage the tin coating.
• Do not touch the contact surfaces after they have been cleaned.

This manual is related to the following products: