6  Electrical connection

SMA America, LLC

56

DISU_SCUS-IA-IUS111711

Installation Guide

6.5.2 Connecting protective earth to busbar

You can connect up to 4 PE cables to the busbar(s). For every PE cable carry out the following
instruction.

1. Strip the PE cable by about 1 

1

5

 in. (30 mm).

2. Open the screw terminal completely.
3. Plug the copper inner conductor of the PE cable into

the screw terminal.

4. Tighten the screw terminal with a torque wrench

and a torque of 41 ft-lb. (56 Nm).