Preparing the Disconnect Unit for Installation

SMA America, LLC

30

DISU_SCUS-AP-eng-IUS110911

Unpacking

1. Screw the grounding strap in the bottom left corner

of the Disconnect Unit to the front plate of the
enclosure. Tighten screw with a torque of 71 in-lbs.
(8 Nm).

2. Tip the front plate over with two persons so that the

upper edge is pointing towards the Disconnect Unit.
Hook the front plate of the enclosure onto the two
hooks on the front of the Disconnect Unit.

3. Press the lower edge of the front plate of the

enclosure onto the Disconnect Unit.

4. For each of the switch handles on the front of the front plate: Shake the handles gently a few

times so that the switch shaft engages with the handle.

$"65*0/

Danger of crushing caused by heavy front plate!

• Note the weight of the front plate 110 lbs. (50 kg).
• Move the front plate of the Disconnect Unit with at least two persons.
• Ensure that one person is holding the front plate of the enclosure at all times when the other

person is working on it.