3 managing small plants with sunny explorer – SMA SPEEDWIRE V.1.1 User Manual
Page 23

SMA Solar Technology AG
6 Commissioning
Installation Manual
SPW-WebconPB-IA-en-11
23
• Set the following parameters in Sunny Explorer (for setting parameters in a device, see
Sunny Explorer help):
• In the field Application-ID, enter the Application-ID of the network operator gateway.
You will receive this value from your network operator. You can enter a value between
0 and 16384. The value 16384 indicates deactivation.
• In the field Goose-Mac address, enter the MAC address of the network operator
gateway from which the Piggy-Back is to receive control commands. You will receive this
value from your network operator. If all MAC addresses are to be accepted in the
adjustable domain, enter 01:0C:CD:01:02:00.
6.3 Managing Small Plants with Sunny Explorer
6.3.1 Functions and Parameter Settings in Sunny Explorer
The following functions for plant management in Sunny Explorer are available:
• Overview of the plant status
• Graphic display of key plant data, device data and energy values
• Parameterisation of individual devices or an entire device class
• Simple diagnostics thanks to the display of faults and events
• Data export of inverter energy values and events in CSV format
• Piggy-Back update
You can change the following parameters in Sunny Explorer:
• Device name of the inverter
• Automatic IP configuration On/Off
• DNS-IP, gateway IP, IP address, subnet mask
• Webconnect function On/Off
• IEC 61850 configuration for plants in Italy up to 6 kW
External Communication > IEC 61850 configuration
Parameter
Value/Range
Resolution
Default
Application-ID
0 to 0x4000
1
0x4000
Goose-Mac address
01:0C:CD:01:00:00
…
01:0C:CD:01:02:00
1
01:0C:CD:01:02:00