10 Troubleshooting
SMA Solar Technology AG
Earthfault
The electrical insulation between the PV plant and earth is defective.
The resistance between the positive or negative DC connection and
earth is outside the permissible range.
Corrective measures:
• Ensure that the PV plant is insulated correctly.
• Ensure that there is no earth fault Checking the PV Plant for Earth
Faults.
Riso-Sense
The insulation measurement has failed.
Corrective measures:
• If this message is displayed frequently, contact the
SMA Service Line.
ROM
The inverter firmware is faulty.
Corrective measures:
• If this message is displayed frequently, contact the
SMA Service Line.
SD-DI converter
The inverter has detected an insulation fault on the DC side.
Corrective measures:
• Ensure that the PV plant is insulated correctly.
• Ensure that there is no earth fault Checking the PV Plant for Earth
Faults.
SD-Imax
The inverter has detected an overcurrent on the AC side. The inverter
disconnects from the electricity grid for safety reasons and afterwards
tries to reconnect to the grid.
Corrective measures:
• If this message is displayed frequently, contact the
SMA Service Line.
SD-WR-Bruecke
The inverter has detected a fault in the power electronics. The inverter
disconnects from the electricity grid for safety reasons and afterwards
tries to reconnect to the grid.
Corrective measures:
• If this message is displayed frequently, contact the
SMA Service Line.
Shutdown
Temporary inverter fault
Corrective measures:
• Contact the SMA Service Line.
Message
Cause and corrective measures