beautypg.com

H3C Technologies H3C S5800 Series Switches User Manual

Page 11

background image

7

from the outside of the building, you may add a dedicated
lightening arrester at the input end of the cable.

To enhance lightening protection, you may need to add a power
lightening arrester at the input end.

Wear an ESD-preventive wrist strap when installing the RPS unit,
and make sure that the wrist strap makes good skin contact.

To avoid electric shock, NEVER open the chassis of the RPS unit
while it is in operation; try not to open the RPS unit even if it is not
electrified.

Unplug the power cord before cleaning the RPS unit.

Keep the equipment room clean. The limits on the concentrations of
dust and harmful gases in the equipment room are shown in the
following tables:

Table 3 Limit on dust concentration

Mechanical active
material

Limit (particles/m³)

Dust particles

≤ 3 × 10

4

(No visible dust on tabletop over

three days)

Note: Dust particle size ≥ 5μm

Table 4 Limits on harmful gas concentration

Gas Limit

(mg/m

3

)

SO

2

0.2

H

2

S 0.006