Chapter 7: Appendix

63 of 78

7-6 Typical Ductwork for Air-Cooled Chillers

*See specification tables on pages 45-48 for air flow and pressure capacities.
When locating your air-cooled portable chiller and designing its ductwork, note any potential high
temperature conditions when discharging into your building and any negative pressures with the building
when discharging air outside.
Notes:

• Customer use of ductwork requires the high pressure fan option for models 5 through 15 hp. •

Allow 30” (77 cm) minimum clearance around the chiller footprint to facilitate free passage of cooling air
and service accessibility

• Size the ductwork for maximum capacity • Support ductwork from the

building structure, not off of the chiller

• Back draft damper to outside must be closed at all times when

fan/blower is not operating

• Chillers with dual fans/blower must have a back draft damper on the cycling

fan/blower to prevent recirculation of hot discharge air

• Chillers are designed to operate at a condensing

entering air temperature of 60ºF (16ºC) minimum

• Maximum total static pressure drop external to the

chiller must not exceed 0.30” WG (75 pa)