AEC 2-40 HP Portable Chillers User Manual
Page 58

2-40 HP Portable Chillers
Chapter 7: Appendix
57 of 78
Remote Condenser Assembly Models
To convert inches to cm, multiply dimension by 2.54.
Fan(s) d e f
Remote Condenser
Refrigeration g
Each
Totals e f
Overall Dimensions
Connections
Charge
HP Dia.
Motor
Amps
Air
flow
Net
wt.
Length Width Height
Mtg. Discharge Liquid
R-22
in.
hp c
460V Fans cfm h lbs.h ‘A’(in.) ‘B’(in) ‘C’(in.) ‘D’(in) ODS(in.) ODS(in.) lbs. g
5
26
3/4 hp 1 ø
2.4
1
6,450 260
49.8
43.0
40.5
40.0
11/8
7/8
3.6
7.5
26
1/3 hp 3 ø
3.7
2
12,400 470
69.8
43.0
40.5
60.0
11/8
7/8
3.6
10
26
1/3 hp 3 ø
3.7
2
13,700 510
89.8
43.0
40.5
80.0
13/8
11/8
4.6
15
26
1/3 hp 3 ø
5.0
3
20,500 550
129.8
43.0
40.5
120.0
15/8
11/8
6.4
20
30 1 1/2 hp 3 ø
5.9
2
23,000 840
125.0
45.5
50.0
108.0
15/8
15/8
10.0
25
30 1 1/2 hp 3 ø
5.9
2
21,900 860
125.0
45.5
50.0
108.0
15/8
15/8
16.0
30
30 1 1/2 hp 3 ø
9.4
3
34,800 1,280
180.0
45.5
50.0
i
21/8
21/8
24.0
35
30 1 1/2 hp 3 ø
9.4
3
32,900 1,300
180.0
45.5
50.0
i
21/8
21/8
24.0
40
30 1 1/2 hp 3 ø 12.9
4
46,400 1,690
235.0
45.5
50.0
i
21/8
21/8
29.0
c
ø represents electrical phase; all motors are 1,140 rpm. Multiply hp by 0.746 to convert to kW.
d
All first fan motors (Header Side) are ¾ hp (0.56 kW) single phase variable speed.
e
Multiply 460V amperages by 2.0 for 208-230V amperages.
f
Multiply 460 V amperages by 0.8 for 575 V amperages.
g
Refrigeration charge is for remote condenser only!
h
To convert cfm to cmh, multiply by 1.699. To convert lbs. to Kg, multiply by 0.454.
i
See drawing above.