Chapter 4: Operation

4-1 Panel Buttons, Indicator Lights, and Switches

Microprocessor Controllers
Standard chillers use a microprocessor-based PID controller. These controllers are modular,
self-contained units that can slide from their mounting housing. They are factory set and
adjusted; no field adjustment to the internal controls are necessary. Their standard operation
range is 30ºF to 65ºF (-1ºC to 18ºC). See Figure 7: Typical Portable Chiller Microprocessor
Controller.

E5CK Controller

Indicator

Name

Description

PV

8.8.8.8

Process Value LED

During normal operation, the large red PV LED
on the controller displays the actual process
temperature at the “To Process” thermocouple. It
also lists parameter symbols during setup and
error messages if an error occurs

SV

8.8.8.8

Set Value LED

During normal operation, the green SV LED on
the controller displays the process set point you
want the chiller to maintain. It also displays
parameter and pre-set function values during set
up.

OUT1

Out 1 LED

The orange OUT1 LED lights when the control
output energizes the hot-gas bypass solenoid valve

OUT2

Out 2 LED

The orange OUT2 LED lights whenever the
process temperature is two degrees or more above
the “To Process” setpoint. The compressor then
comes on and runs until the temperature at the “To
Process” thermocouple is two degrees below the
setpoint.

MANU

MANU LED

The orange MANU LED is not used and does not
light.

STOP

Stop LED

The orange STOP LED is not used and does not
light.

RMT

RMT LED

The orange RMT LED is lit during remote
operation.

AT

AT LED

The orange AT LED flashes during auto-tuning.