2-40 HP Portable Chillers

Chapter 7: Appendix

60 of 78

Water Pressure Drop Tables

Note:

A recirculation pump is required for flows greater than the
maximum or less than the minimum indicated.

Note:

Process flow less than or greater than the flow rates shown below
requires a recirculation pump.

Pressure drops in

P, psig and kPa

2 HP

3.5 HP

5 HP

7.5 HP

Flow

P

Flow

P

Flow

P

Flow

P

gpm

lpm

psig

kPa

gpm

lpm

psig

kPa

gpm

lpm

psig

kPa

gpm

lpm

psig

kPa

4.06

15.4

3.5

24.1

8.03

30.4

4.0

27.6

10.0

37.9

1.5

10.5

12.0

45.4

2.3

16.1

6.01

22.8

7.0

48.3

10.00

37.9

6.5

44.8

12.0

45.4

2.2

14.8

16.0

60.6

2.9

20.1

8.02

30.4

11.5

79.3

12.00

45.4

10.0

69.

18.0

68.1

4.7

32.1

20.0

75.7

5.0

34.5

10.00

37.9

18.0

124.1

14.00

53.0

13.0

89.6

24.0

90.8

7.3

50.2

24.0

90.8

6.9

47.4

16.00

60.6

18.0

124.1

28.0

106.0

9.6

65.9

33.0

124.9

12.7

87.8

10 HP

15 HP

20 HP

25 HP

Flow

P

Flow

P

Flow

P

Flow

P

gpm

lpm

psig

kPa

gpm

lpm

psig

kPa

gpm

lpm

psig

kPa

gpm

lpm

psig

kPa

22.0

83.3

4.7

32.6

30.0

113.6

4.5

31.3

40.0

151.4

4.0

27.6

55.0

208.2

5.5

37.9

30.0

113.6

8.28

57.1

40.0

151.4

7.5

51.7

45.0

170.3

4.0

27.6

58.0

219.5

5.8

40.0

38.0

143.8

12.91

89.0

50.0

189.3

12.4

85.2

50.0

189.3

5.0

34.5

61.0

230.9

6.0

41.4

46.0

174.1

16.77 115.6

60.0

227.1

17.8

122.8

52.0

196.8

6.0

41.4

70.0

264.9

8.5

58.6

50.0

189.3

20.00 137.9

70.0

264.9

24.2

166.6

55.0

208.2

6.5

44.8

30 HP

35 HP

40 HP

Flow

P

Flow

P

Flow

P

Flow

P

gpm

lpm

psig

kPa

gpm

lpm

psig

kPa

gpm

lpm

psig

kPa

gpm

lpm

psig

kPa

72.0

272.5

6.0

41.1

38.7

146.5

1.5

10.4

92.6

350.5

7.9

54.5

44.7

169.2

2.0

13.8

75.0

283.9

6.5

44.8

51.2

193.8

2.6

17.9

107.1

405.4

10.4

71.7

58.5

221.4

3.4

23.4

80.0

302.8

8.0

55.2

62.3

235.8

3.8

26.2

70.9

268.3

4.9

33.8

85.0

321.7

9.5

65.5

71.8

271.7

4.9

33.8

81.6

308.8

6.3

43.5

82.9

313.7

6.5

44.8

105.7

400.0

10.3

71.0

Note:

These pressure drop values are valid for single- and no-pump
portable chillers.

Calculating Chiller Nominal Flow and Pressure to Process

Flow rate: Obtain the flow reading from the appropriate pump curve.
Pressure: Obtain a corresponding pressure reading from the pump curve you selected,

then subtract the one-pump pressure drop listed in the above table using the
appropriate chiller hp and flow rate.

• For two-pump (Process/Recirc) chillers, do not subtract pressure drop from table above

for process pump.