Self Cleaning Continuous Filter Chapter 3: Installation
24
Installing Pressure Gauge
1. Install the differential pressure gauge according to the detailed instruction sheet
packed in the box with your gauge.
2. Mount the gauge in a location that is free from excessive vibration and where the
temperature does not exceed 140°F. Avoid direct sunlight.
3. For permanent installations, it is recommended that ¼” O.D. copper tubing be used
with regular compression fittings. An in-line paper filter will prevent dust from
getting into the gauge line. If this is not used, it is recommended that a loop be
placed in the high pressure gauge line that leads from the dirty air housing so that
dust does not enter the gauge.
4. Adjust the differential pressure gauge to indicate zero.
Figure 13: Connecting Differential Pressure Gauge
Note: Drawing may not depict current unit. Contact manufacturer’s
engineering department for current drawings.