Westermo RM-115S User Manual
Page 56

115S Serial I/O Module
User Manual
Page 56
June 2011
Default settings
If slave address = 0
Modbus RTU, 9600, N, 1
Digital inputs
On-state voltage
<2.1VDC
Wetting current
5mA
Max pulse input rate
1kHz
Minimum pulse width
0.5mS
Max pulse input count
4294967295 (32-bit)
Digital outputs
Output voltage range
0-30VDC
Output current max
200mA
Max pulse output rate
50Hz
Max pulse output count
65535
Analog Inputs
Input voltage range
0-12V
Voltage resolution
16 bits
Input current range
0-24mA
Current resolution
16 bits
Input impedance (voltage)
100k
Input impedance (current)
100ohm
Common mode voltage
range
27VDC
Calibrated accuracy
0.10%
Analog Outputs
Output voltage range
0-12V
Voltage resolution
12 bits
Output current range
0-24mA
Total output current 160mA
Current resolution
12 bits
Calibrated accuracy
0.10%
Table D-1: 115S Specifications.
115S
-11
-12
-13
Digital inputs/outputs
16
8
8
Pulse outputs
8
8
8
Pulse inputs
4
-
-
Analog inputs
-
8
-
Analog outputs
-
-
8
Table D-2: 115S module types and I/O.