Westermo RM-115S User Manual
Page 47
115S Serial I/O Module
User Manual
man_115S_1.14.docx
Page 47
Data
Modbus I/O Type
Modbus
Addresses
Pulse input rate 4
Input registers
30004
Maximum input pulse rate 1
Input registers
30101
Maximum input pulse rate 2
Input registers
30102
Maximum input pulse rate 3
Input registers
30103
Maximum input pulse rate 4
Input registers
30104
Pulse output count 1
Input registers
30009
Pulse output count 2
Input registers
30010
Pulse output count 3
Input registers
30011
Pulse output count 4
Input registers
30012
Pulse output count 5
Input registers
30013
Pulse output count 6
Input registers
30014
Pulse output count 7
Input registers
30015
Pulse output count 8
Input registers
30016
Pulse output target 1
Holding registers
40009
Pulse output target 2
Holding registers
40010
Pulse output target 3
Holding registers
40011
Pulse output target 4
Holding registers
40012
Pulse output target 5
Holding registers
40013
Pulse output target 6
Holding registers
40014
Pulse output target 7
Holding registers
40015
Pulse output target 8
Holding registers
40016
Modbus Output Timeout
Holding registers
40204
Pulse out update time 1
Input registers
30109
Pulse out update time 2
Input registers
30110
Pulse out update time 3
Input registers
30111
Pulse out update time 4
Input registers
30112
Pulse out update time 5
Input registers
30113
Pulse out update time 6
Input registers
30114
Pulse out update time 7
Input registers
30115
Pulse out update time 8
Input registers
30116
Module supply voltage
*
Input registers
30033
Serial port transmission mode
Input registers
30201
Serial port baud rate
Input registers
30202
Serial port parity and stop bit
Input registers
30203
Modbus Comms Fail Timeout
!
Input registers
30204
ELPRO ACK Timeout
!
Input registers
30205
Module Firmware version
%
Input Register
30801
*
0x4000 = 8V; 0xC000 = 40V (Firmware earlier than 2.00 is 0x4000 = 8V; 0xC000 = 16V
!
Timeout values in 32mSec increments
%
0x0204 = Ver 2.04