4 Hardware Configuration


Hardware Set-up allows the 115S hardware function to be adjusted to suit the application.
To configure the hardware settings, you need:

- Access to the DIP switches under the Analog Configuration Panel (refer Figure

1-1: 115S unit with significant parts labeled.)

- Configuration Software to run on your PC.


Configuration of the 115S modules is performed by either the dedicated 115S
configuration software (cfg_115S_Vx.xx.exe), or by the ELPRO E-Series configuration
software (from the Utilities / Advanced - SXM menu). The software is available from
ELPRO’s Product CD or web page

4.1 Connecting to the 115S module


To use the configuration software, perform the following steps:
• Connect the 115S to the PC COM port with a standard serial cable (straight-through,

DB9 female to DB9 male. See Appendix for wiring.)

• Set the address switches to 00

• Supply power to the 115S via the “+” and “-” terminals on the bottom of the module

(10.8-30 VDC **).

** Model Dependent. Check rear label for actual operating voltages

• Start the configuration software on your PC or laptop (cfg_115S_Vx.xx.exe)

Figure 4-1: Main configuration screen.