beautypg.com

2 input data word – Westermo FD-80 User Manual

Page 21

background image

21

6630-2281

Word

15

High

byte

8

7

Low byte

0

1

ST

DV

ACK

TO

2

In word 1, high byte

In word 1, low byte

64

In word 63, high byte

In word 63, low byte

7.2.2.2 Input data word

Data is transmitted from the FD-80 to the Profibus DP master. The first word is the
added status word and the remaining 1 to 63 words are ordinary input data received
from the output word addressed remote Fieldbus Adapter.

Input word 1 high byte (bit 15..8) is the serial transfer status byte, with following con-
tent:

ST

STatus of serial transfer command FD-80 (bit15).
Set to high (1) when the received command has been
accepted by the FD-80. Set to low (0) if the received
command has not been accepted.

DV

Data Valid (bit 13).
For testing purpose only.
Acknowledgement of the command CNF.

ACK

ACKnowledgement of serial transfer (bit 11).
Set to high (1) when serial transfer sent output data to a
remote FD-80 has resulted in a received frame with input
data from the remote FD-80.

TO

Time Out of serial transfer (bit 10).
Set to high (1) when the last serial transfer of output
data to a remote FD-80 has not resulted in any received
frame within 1,500 ms.

Input word 1 low byte (bit 7..0) is not used.

Input word 2 to 64 is the input data, with following content:

Word 1

High: Input byte 1

Low: Input byte 2

Word 2

High: Input byte 3

Low: Input byte 4

........

.........

.......

Word 63

High: Input byte 125

Low: Input byte 126.