Wcc iii installation, Sat 3c controller – WattMaster WCC III part 12 User Manual
Page 52

WCC III Technical Guide
12-50
12. WCC III INSTALLATION
SAT 3C Controller - Connections points
All of the external SAT 3C connection points are single-tab ¼ 
inch Sta-Con connectors. With the exception of the TUC RS-
485 communications connection which is a three-position, de-
pluggable terminal block.
24VAC & GND Connection
Located on the bottom side of the SAT III controller is a 24 VAC 
and GND connection. This is the main power connection to the SAT 
3C controller. Each SAT 3C Controller draws - 10VA. The GND 
connection points must be the same between all of the externally 
powered TUC/RTU boards and the SAT 3C Controller. 
SAT Communication Connection
These connection points are for wiring of the SAT RS-485 
communication loop. There are two “T” (Transmit) connections, 
two “R” (Receive) connections and two “SHIELD” connection 
points. There are two connection points provided for each 
connection for easy “daisy chaining” to the next Satellite Controller. 
When connecting the RS-485 wiring from SAT III to SAT III or 
SAT 3C/D/F, or SAT 3P controller the wiring connections are as 
follows: connect “R” TO “R”, “T” TO “T”, AND “SHIELD” TO 
“SHIELD” OR “SH”. The RS-485 wire specifi cations are plenum 
rated jacketed stranded 18-gauge, 2-wire twisted pair with shield. 
18-gauge stranded wire is mandatory to ensure a good connection 
with the ¼-inch Sta-Con connectors which are used to terminate 
the wires at the WCC III - MCD and at the satellite controllers.
TUC Communication Connection
These connection points are for wiring of the TUC RS-485 
communication loop. There is a single three position, de-pluggable 
terminal block. Connect the wiring for the communications 
connections between the TUC/RTU’s as follows: “R” TO “R”, 
“T” TO “T”, AND “SHLD” TO “SHLD” OR “SH”. Connect the 
wiring from TUC/RTU controller to TUC/RTU controller. But, on 
the SAT 3C/D/F controller the TUC “R” connection must be wired 
to the SAT 3C/D/F “T” connection, and the SAT 3C/D/F controller 
“R” connection must be wired to the TUC “T” connection. The 
RS-485 wire specifi cations are plenum-rated jacketed stranded 
18-gauge, 2-wire twisted pair with shield. 18-gauge stranded wire 
is mandatory to ensure a good connection between TUC/RTU 
controllers.