Wcc iii installation guide, Analog input values, Wcc iii technical guide 12-45 – WattMaster WCC III part 12 User Manual

Page 47

background image

12. WCC III INSTALLATION

GUIDE

WCC III Technical Guide

12-45

The following table shows the required load resistor, Data Pattern,
0 % and 100 % programmed values, Jumper setting, Analog Type,
for the Analog Input Screen. For the Thermistor type sensors, there
are no 0 % or 100 % values to program.

Figure 12-36: Analog Input Values

Analog Input Screen Values

Temperature

Sensor

Load

Resistor

(Ohms)

Data Pattern

% Scale

100% Scale

Jumper

Setting

Analog Type

2-Wire Surface

Mount

100

XXX.X

0.0

100.0

0-1

General

0.0

500.0

0-5

General

2-Wire Flush

Mount

301

XXX.X

0.0

100.0

0-1

General

0.0

500.0

0-5

General

3-Wire Flush

Mount

None

XXX.X

0.0

100.0

0-1

General

0.0

500.0

0-5

General

2-Wire Air/Water

100

XXX.X

0.0

100.0

0-1

General

2-Wire Air/Water

49.9

XXX.X

0.0

200.0

0-1

General

Thermistor Flush

Mount

None

XXX.X

Auto

Auto

THERM

Thermistor

Thermistor Duct

6”

None

XXX.X

Auto

Auto

THERM

Thermistor

Thermistor Duct

6”

None

XXX.X

Auto

Auto

THERM

Thermistor

Thermistor

Outdoor Air

None

XXX.X

Auto

Auto

THERM

Thermistor

Analog Input Values