Scuscr.exe screens, Single duct globals and mode of operation screens, Wcc iii technical guide 4-36 – WattMaster WCC III part 5 User Manual
Page 38
WCC III Technical Guide
4-36
4. SCUSCR.EXE SCREENS
Figure 4-9: Single Duct Cooling Only - Pressure Dependent Mode of Operation Screen
SINGLE DUCT COOLING ONLY VAV BOX
{ TUC-2R }
Satellite: _ 4
Unit:
1
Location:
Version: 2.03
Analog Address Locations
Logic Switch Definitions
A1 - Space Temperature
L1
- Pushbutton Override Status
R1A - Cooling Demand
P1 - Damper Position
VAV BOX MODE OF OPERATION SELECTION
Enter Type of
Box Desired....................................:
0
0 = Single Duct Cooling Only Box
[ Pressure
Dependent ]
1 = Single Duct Cooling Only Box
[ Pressure Independent ]
2 = Parallel Fan Box w/Reheat
[ Pressure
Dependent ]
3 = Parallel Fan Box w/Reheat
[ Pressure Independent ]
4 = Series Fan Box w/Reheat
[ Pressure
Dependent ]
5 = Series Fan Box w/Reheat
[ Pressure Independent ]
6 = Heating/Cooling Changeover
[ Pressure
Dependent ]
7 = Heating/Cooling Changeover
[ Pressure Independent ]
8 = Single Duct Cooling w/Reheat
[ Pressure
Dependent ]
9 = Single Duct Cooling w/Reheat
[ Pressure Independent ]
NOTE:
You must have an Airflow Sensor for Pressure Independent Boxes!
Press < HOME > for Main Menu
Press < Ctrl- Right Arrow > for Status Screen
Single Duct Globals and Mode of Operation Screens