4. SCUSCR.EXE SCREENS
WCC III Technical Guide
4-9
Occupied Mode
If the VAVBOX TUC-2R controller is used on a non-fan-powered 
terminal unit that has reheat, the VAVBOX damper will move 
to the Nite/Reheat position whenever a Space Heating demand 
occurs and the HVAC unit is in Supply Air Cooling or Neutral 
mode. When the HVAC unit is in Supply Air Heating mode, the 
VAVBOX damper will modulate as required to maintain the Space 
Heating setpoint.
Unoccupied Mode
When using non-fan powered terminal units, the VAVBOX damper 
will position itself in the Nite/Reheat minimum position. In order 
for fan powered terminal units to position the damper to the Nite/
Reheat minimum position, the check for main fan status must be 
selected and the HVAC unit fan must be operating.
Occupied Mode Sequences
Space Vent Mode
This mode only applies to the Occupied Mode of operation. If the 
equipment is in the Unoccupied Mode, then a lack of heating or 
cooling demand would generate the Off Mode.
If the HVAC unit is in Supply Air Neutral Mode, you can adjust 
the damper position on pressure dependent terminal units and 
the airfl ow on pressure independent terminal units to provide a 
fi xed amount of ventilation air into the space when there are no 
heating or cooling demands. During this time, the damper does 
not modulate on pressure dependent terminal units. On pressure 
independent terminal units, it only modulates to the extent required 
to maintain the vent minimum airfl ow setting.
If the VAVBOX
Controller detects that the HVAC unit is in Supply Air Heating 
mode, indicating that the air handler has activated its heat, the 
heating airfl ow minimum will be substituted for the vent minimum 
position. If the VAVBOX Controller detects that the HVAC unit 
is in Supply Air Cooling mode, indicating that the air handler 
has activated its cooling, the cooling airfl ow minimum will be 
substituted for the vent minimum position.
Space Cooling Mode
Occupied Space Cooling mode is initiated by the temperature in 
the space rising above the Occupied Cooling Setpoint.
If the VAVBOX TUC-2R controller is in the Supply Air Heating 
mode and another VAVBOX TUC-2R controller has a cooling 
demand, the damper/airfl ow for the VAVBOX TUC-2R controller 
requiring cooling will position itself to provide the heating 
minimum setpoint amount of air into the space. No modulation 
open will occur because the space does not want the warm air 
currently being supplied by the air handler.
When the VAVBOX TUC-2R controller is in the Supply Air 
Cooling mode, the damper is normally held at the minimum 
cooling position until the space temperature begins to rise above 
the cooling setpoint. As the space temperature rises to within 0.5 ºF 
of the Occupied Cooling Setpoint, the damper/airfl ow calculation 
causes the air valve to open proportionally until the maximum 
setpoint is achieved at 1.5 ºF above the setpoint. This is a 2 ºF 
proportional window starting 0.5 ºF below the cooling setpoint to 
1.5 ºF above the cooling setpoint.
The damper/airfl ow is never allowed to modulate outside the 
user adjusted minimum setpoint and the maximum setpoint. The 
maximum damper/airfl ow setpoint applies to heating and cooling 
modes of operation only. All of the modes have their own individual 
minimum setting.
Series Flow Fan Terminals
If the VAVBOX TUC-2R controller has been confi gured as a Series 
Fan Powered terminal unit, the series fan relay will activate and 
run the series box fan continuously anytime the VAVBOX TUC-
2R controller is in occupied mode.
In all cases, before the series box fan can be activated, the air 
damper is driven fully closed and held that way for 30 seconds to 
make sure the series box fan hasn’t inadvertently started to spin 
backwards. Once the series box fan starts, it waits an additional 
10 seconds to allow the fan to spin up before it starts to open the 
damper and introduce airfl ow from the HVAC unit fan.
Parallel Flow Fan Terminals
During normal cooling or vent mode and adequate air supply, 
the parallel fan will be off. During the occupied cooling or 
vent mode, the Parallel fan will only activate if the damper/
airfl ow is below a user defi ned low limit setting. This causes it 
to be used as a make-up air source. When the damper/airfl ow 
rises 15% above the low limit setpoint, the Parallel fan will be 
deactivated.
The check for main fan status setting has no effect on the 
Parallel Fan box when in the occupied mode.
Space Heating Mode
Occupied Space Heating mode is initiated by the temperature in 
the space falling below the Occupied Heating Setpoint.
If the VAVBOX TUC-2R controller is in the Supply Air Cooling 
mode and another VAVBOX TUC-2R controller has a heating 
demand, the damper/airfl ow for the VAVBOX TUC-2R controller 
requiring heating will position itself to provide the Cooling 
Minimum amount of air into the space. No modulation open will 
occur because the space does not want the cold air currently being 
supplied by the air handler.
WCC III VAV BOX III Operation Modes