4. SCUSCR.EXE SCREENS
WCC III Technical Guide
4-27
VAV BOX CONTROLLER
Satellite: _ 4
Unit:
1
Location:
Version: 3.04
[ MODE OF OPERATION ]
Enter the proper control method for the type of box installed:
3
0 = Single Duct Cooling Only
1 = Heating/Cooling Changeover
2 = Series Fan Powered
3 = Parallel Fan Powered
NOTE: Boxes will automatically operate as Pressure Independent if the
Box Size Contant is greater than 0 CFM.
Screen File: SCR220.SDF
< Ctrl- Right Arrow > for Previous Page
Figure 4-5: VAV BOX Mode of Operation Screen
VAV BOX Mode of Operation Screen
VAV Box Control Method
Set this setup confi guration item for the type of box that the
VAVBOX TUC-2R controller is to be used on. The options
available are:
0 = Cooling Only Box
1 = Heating/Cooling Changeover Box
2 = Series Fan Powered Box
3 = Parallel Fan Powered Box
The Cooling Only VAV BOX controllers have the option of having
Reheat only if the expansion board is installed.