7.2.2 Control Data Word - data word 10 (PLC

MC100)

DW 10

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

PS

P7

P6

P5

P4

P3

P2

P1

-

-

-

N4

N3

N2

N1

N0

N4-0

DW12-21

Comments

0

Not Used

1

Request for MC100 FBM Version

2

Application Name

3

Pump version

For the active pump selected in DW0

4

Alarm text strings

Text string for the pending alarm

5

Warning text strings

Text string for the pending warning

6

Reserved

7

Reserved

8

Reserved

9

Reserved

10

Tube table for active pump

Tube table consisting of 10 bytes with tube
diameters.

6


N4-0 Selects the parameters type to be received in DW 12-21 if text string is requested.

P7-1 is set if the corresponding parameter has a new value to be send to the active pump

(selected in DW0)

P1: A new value for the volume is set in word 12 and 13 is ready to be retrieved by the MC100

P2: A new value for the tube size is set in word 14 is ready to be retrieved by the MC100

P3: A new value for the speed is set in word 15 is ready to be retrieved by the MC100

P4: A new value for the acceleration is set in word 16 is ready to be retrieved by the MC100

P5: A new value for reverse is set in word 17 and is ready to be retrieved by the MC100

P6: A new value for density is set in word 18 and 19 and is ready to be retrieved by the MC100
P7: A new value for calibration is set in word 20 and 21 and is ready to be retrieved by the
MC100

You can send more parameters to a pump in one data package – e.g. when sending a new recipe.

PS

is set to request a test string in DW12 to 21. The data is selected in N4 – N0 as described

above.
Please remember to reset the flags when the data has been received by the MC100.

6

Tube diameter is an integer value with a hidden decimal point - e.g. 16 equals 1.6 mm ID