beautypg.com

Users manual, Mc100 – Watson-Marlow MC100 User Manual

Page 24

background image

Users Manual

MC100

MC100 Users Manual Profibus DP - rev 4

Rev. 4

Page 24 of 40

7.1.5 Process status bits from the pumps – word 1 to 9 (MC100

PLC)


For each pump address (1 to 16) one byte is dedicated for status bits. I.e. one data word holds the
status bits for two pumps.
Regardless of the number of pumps attached to the MC100 all pump control words has to be sent. The
data for pumps not available are ignored.

Word 8

Word 7

Word 6

Word 5

Word 4

Word 3

Word 2

Word 1

P16 P15 P14 P13 P12 P11 P10

P9

P8

P7

P6

P5

P4

P3

P2

P1


Bit mapping in each status byte (P1 to P16):

7

6

5

4

3

2

1

0

ALARM

Direction

DONE

Pump

Dispense Tube Br.

BUSY

READY


Bit 0:

READY

Pump is ready (self check is OK).

Bit 1:

BUSY

1 Indicate that the pump is active, either dispensing or pumping

0 the pump is idle

Bit 2:

Tube Br.

Tube bridge bit:

1 = tube bridge on

0 = tube bridge off.

Please note that due to security reasons the pump cannot run if the tube bridge
is off. This is controlled by the pump controller.

Bit 3:

Dispense

Dispense bit:

1 = dispense mode

Bit 4:

Pump

Pump bit:

1 = pump mode

Bit 5:

DONE

4

Is set when pump goes from dispensing to idle / reset by a new START bit.

Bit 6:

Direction

Handshake for bit B5 from command byte (0=normal / 1=reverse direction.)

Bit 7:

ALARM

See Chapter 7.3.2.1.1 for further information


4

The DONE bit can be necessary to use if there is very short filling times, where the BUSY signal is not detected because of

transmission times on the fieldbus network.