7.1.4 Process control bits for the pumps– word 1 to 9 (PLC

MC100)



For each pump address (1 to 16) one byte is dedicated for control bits. I.e. one data word holds the
control bits for two pumps.
Regardless of the number of pumps attached to the MC100 all pump control words has to be sent. The
data for pumps not available are ignored.

Word 8

Word 7

Word 6

Word 5

Word 4

Word 3

Word 2

Word 1

P16 P15 P14 P13 P12 P11 P10

P9

P8

P7

P6

P5

P4

P3

P2

P1


Bit mapping in each command byte (P1 to P16):

7

6

5

4

3

2

1

0

Direction

Disable in

Par./Serial

RESET

PUMP

DISP

START


Bit 0: START

Start a single Dispense cycle, when the Pump is set in Dispense mode (Bit. 1)
This bit must be cleared upon receiving the BUSY bit in the status byte for the pump,
see below.

Bit 1: DISP

Sets the pump in dispense mode and thereby enables the START bit to start
dispenses. If removed during dispensing the pump stops immediately.

Bit 2: PUMP

2

Starts pump running continuously with the set speed.

Bit 3:

Reserved for future use

Bit 4: RESET

To be used with future pumps

Bit 5:

Disable pump in parallel and serial mode. If set high the pump will ignore dispense

and pump bites.

Bit 6: Direction

3

[1/0] [Backwards/Normal] pump and dispense direction.

Bit 7

Reserved for future use

2

The DISP bit has higher priority and must be cleared before setting the PUMP bit.

3

Available for pumps able to handle this function (GD30).