General Information

Effective Installation of Cables

In order to minimize any air loss from under the raised-floor plenum, allow for adequate
slack in the cables. If the cables are under too much tension, the grommet filaments may
be pulled apart, resulting in a V-shaped gap that will cause an increase in the volume of air
escaping from under the raised floor.


Cutting Raised Floor Tiles

Each raised floor tile manufacturer provides instructions to properly and safely modify their
products. Installers must be familiar with and observe tile manufacturer’s recommendations
with regard to applicable tools, cutting procedures, the design load capacity of the cut tile,
and any additional underfloor support requirements for cut raised floor tiles.
When installing the KoldLok Extended Raised Floor Grommet on a newly cut hole, trim
the cutout prior to installation to protect cables from damage.


Maintaining Proper Cooling of Equipment

Failure to follow computer manufacturer’s guidelines for maintaining proper cooling may
result in the overheating of equipment. Ensure that there is adequate airflow to the intake
side of the computer equipment or cabinets through devices such as perforated floor tiles or
grates. Achieving proper airflow to the intake side of computer equipment and/or cabinets is
the responsibility of the customer.

Safety Requirements

Installers must be familiar with standard safety and risk management practices when work-
ing on server rack equipment or in data center environments.