Installation of KoldLok Wave™ on the Tile Edge—Long Edge of Grommet
In the absence of a supporting floor tile flange, edge-mount installations require a
foam insert on the open side of the cut to serve as a gasket. If the hole in your floor tile
has been cut on three sides only, providing one open edge, the grommet must be
installed with the supplied foam strip inserted into the molded depression on its
underside.
1.
Provide a 9 1⁄4 x 7 1⁄2 ” (± 1/16”) cutout or 235mm x 200mm (± 2mm) in the floor
tile. Ensure that any burrs that resulted from cutting the floor tile have been
removed. A cutout template is available for download at
www.KoldLokWave.com. It is not necessary to dress the cutout when
installing a KoldLok Wave™ Split Integral Grommet.
2.
Stretch the supplied foam
strip to fill the 9” depres-
sion on the underside of
the grommet.
3.
Test-fit KoldLok Wave ™ to
the floor tile, with flange
on the topside of the floor
tile. Ensure there is no
binding and that the fit is
even on the grommet.
4.
With the grommet
properly placed in the
floor tile, fasten it securely
to the floor tile using the
self-tapping screws. Do
not over-torque the screws.
Installation of KoldLok Wave™ on the Tile Edge—Short Edge of Grommet
The KoldLok Wave™ Split Integral Grommets may also be installed with the short side
mounted along the floor tile edge. Make a 10 1⁄8 x 6 3⁄4” (± 1/16”) cutout or 257mm x
171mm (± 2mm). Follow the same cleaning and fastening steps as above.