Installation of KoldLok Wave™ on the Tile Edge—Long Edge of Grommet

In the absence of a supporting floor tile flange, edge-mount installations require a

foam insert on the open side of the cut to serve as a gasket. If the hole in your floor tile

has been cut on three sides only, providing one open edge, the grommet must be

installed with the supplied foam strip inserted into the molded depression on its

underside.

1.

Provide a 9 1⁄4 x 7 1⁄2 ” (± 1/16”) cutout or 235mm x 200mm (± 2mm) in the floor

tile. Ensure that any burrs that resulted from cutting the floor tile have been

removed. A cutout template is available for download at

www.KoldLokWave.com. It is not necessary to dress the cutout when

installing a KoldLok Wave™ Split Integral Grommet.

2.

Stretch the supplied foam

strip to fill the 9” depres-

sion on the underside of

the grommet.

3.

Test-fit KoldLok Wave ™ to

the floor tile, with flange

on the topside of the floor

tile. Ensure there is no

binding and that the fit is

even on the grommet.

4.

With the grommet

properly placed in the

floor tile, fasten it securely

to the floor tile using the

self-tapping screws. Do

not over-torque the screws.

Installation of KoldLok Wave™ on the Tile Edge—Short Edge of Grommet

The KoldLok Wave™ Split Integral Grommets may also be installed with the short side

mounted along the floor tile edge. Make a 10 1⁄8 x 6 3⁄4” (± 1/16”) cutout or 257mm x

171mm (± 2mm). Follow the same cleaning and fastening steps as above.