Heat transfer compounds, Snaptrace – Thermon Heat Transfer Compounds User Manual
Page 6
Heat Transfer Compounds
5
SnapTrace
®
. . .
Installation on Straight Run Piping
Tracers are to be run parallel and in direct contact with the
process pipe where possible. Tracer location on pipe is to be
where most accessible. If more than two tracers are used,
they should be equally spaced circumferentially around the
pipe as shown in Illustration G.
1. Install tube or pipe tracers in accordance with Illustration
A (see T-3 and T-99 installation). Pressure test tracing for
leaks with steam pressure equal to or greater than the nor-
mal operating pressure or preferably with suitable hydro-
static tests. Repair any leaks and retest until tracing system
is free of leaks.
2. Place SnapTrace over tracer as shown in Illustration F be-
low.
Illustration F: Installation of SnapTrace
Compound
Place SnapTrace and channel over tracer.
Band SnapTrace to pipe (see Illustration A).
SnapTrace or
Compound
Tracer
Stainless Steel
Banding and Seals
Insulation
TFK Channel
Triple Tracer
Dual Tracer
Single Tracer
Stainless Steel
Banding
Process Pipe
Temporary
Stainless Steel
Tie Wire
TFK Channel
SnapTrace
Tracer
Tube
Crimp Seal
3. Position TFK channel over SnapTrace.
4. Attach channel to process piping with stainless steel
banding and crimp-type seals as shown.
• Banding should be a minimum of 12 mm x 0.5 mm for
ST-1 and ST-2 systems.*
• Banding should be a minimum of 12 mm x 0.5 mm for
ST-3, ST-4, ST-5 and ST-6 systems.*
• Banding tool should exert a force of 4450 N or greater.*
* Banding, crimp seals and tools meeting the required specifications are available
from Thermon.
5. Insulate and weatherproof piping.
Illustration G: SnapTrace and ChannelTrace™
75 mm
Minimum
120°
120°
120°
Note . . .
For ease of installation and serviceability, all tracers shall be installed parallel to and
against the heated pipe or equipment and shall be placed on the most accessible sur-
face location in regard to supports, ease of installation, connection and thermal insula-
tion. Multiple tracers shall be equally spaced around the circumference of the pipe.
45°
45°
380
mm
380
mm