beautypg.com

Máximo mínimo – Tecfluid LD60 User Manual

Page 4

background image

ELECTRICAL CONNECTION

The LD-60 can be installed as a detector of minimum or maximum level. The electrical connection
is made by means of a DIN 43650-A connector with a PG-9 cable gland. Multiple conductor cable
with sections about 0,5 mm

2

should be used.


To open the connector, remove the centre screw and prise open using a small screwdriver in the
slot shown in the following drawing (looking at the female connector from the contact side).

The working mode (maximum or minimum) is chosen by means of the cable connection, as
shown in the following figure.

1

2

3

1
2

3

L

L

N

N

Tierra

Ca rga

Ca rga

Tierra

Máximo

Mínimo

a) DC version.

1

2

3

1
2

3

-

-

+

+

Tierra

Tierra

Máximo

Mínimo

Ranura de apertura

4

b) AC version.

NOTE: The AC version has a power consumption of 6 mA when the load is deactivated.
This should be taken into account when the load is a relay. You must make sure that the
dropout voltage of the relay is greater than the voltage across the coil when a current of 6
mA flows through it. If the dropout voltage is equal or smaller then the relay can be in an
activated position independent of the LD-60 state.

Slot to open the connector

Maximum

Minimum

Maximum

Minimum

Load

Load

Earth

Earth

Earth

Earth