Model 9120 Redundant Probe System - Color
4580 – Redundant Probe System – Color
Page 10 of 23
the alarm relay and switch probes when an out-of-band condition is detected.
Note - There is a 950 mV
low limit for an alarm. This condition is typically found during a burnoff, so the alarm will not
be active when the input drops below 950 mV
.
The range is 0 to 9999.
Selected Probe
Indicates which probe is selected.
Note – This field is only editable when the Probe select mode
(below) is set to no auto switch
. The options are: 1 or 2.
Probe select mode
This determines how the specified probe is selected. The options are: highest mV, lowest mV, or no
auto switch (manual mode).
Communications Setup
This menu option will allow the user to configure
the communications settings for the RPS unit.
Note – It is strongly recommended that
none of these settings be modified without
assistance from Super Systems at 800-
666-4330
.
RS-232B Baud
This will allow the user to set the RS-232B baud
rate.
Note – This must be set to 19200 for
the Touchscreen
.
If the Baud rate is switched, the screen
will no longer communicate with the
instrument, and the RPS unit will need to
be returned to Super Systems, Inc for
repair. The Baud rate should be fixed at
19200
.
The options are:
1200
14400
57600
2400
19200
76800
4800
28800
115200
9600
38400
RS232B Mode
This will allow the user to set the RS232B mode.
Note – This must be set to Modbus for the
Touchscreen
.
If the Mode is switched, the screen will no longer communicate with the instrument, and the
RPS unit will need to be returned to Super Systems, Inc for repair. The Mode should be fixed
at Modbus
.
The options are: Modbus master or Modbus.
RS-232A Baud
This will allow the user to set the RS-232A baud rate.
Note – This must be set to 19200 for the
Touchscreen
.
If the Baud rate is switched, the screen will no longer communicate with the instrument, and
the RPS unit will need to be returned to Super Systems, Inc for repair. The Baud rate should
be fixed at 19200
.
The options are:
1200
14400
57600