ERROR MESSAGES
OVERRANGE, UNDERRANGE AND SENSOR LEADS
BREAK INDICATIONS
The device is capable to detect a fault on the process
variable (OVERRANGE or UNDERRANGE or SENSOR
LEADS BREAK).
When the process variable exceeds the span limits
established by configuration parameter P 1 an
OVERRANGE condition will be shown on display as
shown in the following figure:
An UNDERRANGE condition will be shown on display as
shown in the following figure:
When P41 is different from zero and an out of range
condition is detected, the instrument operates in
accordance with P41 and P42 parameters.
When P41 is equal to 0 (standard effect) and time
proportional outputs are configured, the following
conditions may occur:
- The instrument is set for one output only and an
OVERRANGE is detected, the OUT 1 turns OFF (if
reverse action) or ON (if direct action).
- The instrument is set for heating/cooling action and an
OVERRANGE is detected, OUT 1 turns OFF and OUT 3
turns ON.
- The instrument is set for one output only and an
UNDERRANGE is detected, the OUT 1 turns ON (if
reverse action) or OFF (if direct action).
- The instrument is set for heating/cooling action and an
UNDERRANGE is detected, OUT 1 turns ON and OUT
3 turns OFF.
F.CAL
see "Feedback potentiometer calibration".
POS.L
see "Feedback potentiometer calibration"
Fb.LC
see "Feedback potentiometer calibration"
POS.H
see "Feedback potentiometer calibration"
Fb.HC
see "Feedback potentiometer calibration"