P9 = Alarm 2 function (OUT 4).
nonE =

output not used.

AL2.P =

it is used as Alarm 2 output and the alarm 2 is
programmed as process alarm.

AL2.b =

it is used as Alarm 2 output and the alarm 2 is
programmed as band alarm.

AL2.d =

it is used as Alarm 2 output and the alarm 2 is
programmed as deviation alarm.

NOTE: The alarm 2, the alarm 3 and the "Loop break
alarm" are in OR condition on the same output (OUT 4)
but the alarm 3 and the "Loop break alarm" are mutually
exclusive.

P10 = Alarm 2 operating mode
Available only when P9 is different from "nonE".
H.A. = High alarm (outside for band alarm) with

automatic reset.

L.A. =

Low alarm (inside for band alarm) with automatic
reset.

H.L. =

High alarm (outside for band alarm) with manual
reset (latched).

L.L. =

low alarm (inside for band alarm) with manual
reset (latched).

P11 = Alarm 3 function (OUT 4)
nonE =

output not used.

AL3.P =

it is used as Alarm 3 output and the alarm 3 is
programmed as process alarm.

AL3.b =

it is used as Alarm 3 output and the alarm 3 is
programmed as band alarm.

AL3.d =

it is used as Alarm 3 output and the alarm 3 is
programmed as deviation alarm.

NOTE: The alarm 2, the alarm 3 and the "Loop break
alarm" are in OR condition on the same output (OUT 4)
but the alarm 3 and the "Loop break alarm" are mutually
exclusive.

P12 =

Alarm 3 operating mode and loop
break alarm reset type

Available only when P11 is different from "nonE" or P51 is
different from "diS".
H.A. = High alarm (outside for band alarm) with

automatic reset.

L.A. =

Low alarm (inside for band alarm) with automatic
reset.

P6 = Valve position indication.
This parameter is available only if P5 = Sñ.OL
Fb =

the valve position will be displayed

no.Fb = the valve position will not be displayed (the feed-

back potentiometer can be omitted)

P7 = Output 3 function.
nonE =

output not used.

AL1.P =

it is used as Alarm 1 output and the alarm 1 is
programmed as process alarm.

AL1.b =

it is used as Alarm 1 output and the alarm 1 is
programmed as band alarm.

AL1.d =

it is used as Alarm 1 output and the alarm 1 is
programmed as deviation alarm.

rEv =

it is used as second time proportional control
output with reverse action.

dir =

it is used as second time proportional control
output with direct action.

NOTES:
1)

If P7 is changed to "rEv" the cycle time (Cy3) will be
forced to 15 s

2)

If P7 is changed to "dir" the cycle time (Cy3) will be
forced to:

10 s when P25 = Air
4 s when P25 = OIL
2 s when P25 = H2O

3)

Only one of the two outputs (see P5 and P7) can be
configured as "rEv" control output.

4)

Only one of the two outputs (see P5 and P7) can be
configured as "dir" control output.

5)

If the servomotor output is selected (P5 ="Sñ.OL" or
"Sñ.CL") the OUT 3 can be set as alarm output only (P7
= "AL1.P" or "AL1.b" or "AL1.d").

P8 = Alarm 1 operating mode
Available only when P7 is equal to AL1.P, AL1.b or AL1.d.
H.A. = High alarm (outside for band alarm) with

automatic reset.

L.A. =

Low alarm (inside for band alarm) with automatic
reset.

H.L. =

High alarm (outside for band alarm) with manual
reset (latched).

L.L. =

low alarm (inside for band alarm) with manual
reset (latched).