OPERATIVE PARAMETERS
Push the FUNC pushbutton, the lower display will show
the code while the upper display will shows the value or
the status (ON or OFF) of the selected parameter.
By
s or t pushbutton it is possible to set the desired
value or the desired status.
Pushing the FUNC pushbutton, the instrument memorizes
the new value (or the new status) and goes to the next
parameter.
Some of the following parameter may be skipped
according to the instrument configuration.
Param.
DESCRIPTION
SP
Set point (in eng. units).
Range: from rL to rH.
SP is operative when logic inputs 1 and 3 are
open.
Sñrt
SMART status.
The On or OFF indication shows the actual
status of the SMART function (enabled or
disabled respectively).
Set On to enable the SMART function.
Set OFF to disable the SMART function.
ñ.rSt
Manual reset of the alarms.
This parameter is skipped if none of the alarms
have the manual reset function.
Set On and push FUNC to reset the alarms.
SP2
Set point 2 (in eng. units).
Range: from rL to rH.
SP2 is operative when logic input 3 is open
while the logic input 1 is closed.
and P50 is different from 0.
SP3
Set point 3 (in eng. units).
Range: from rL to rH.
SP3 is operative when logic input 3 is closed
while the logic input 1 is open and P50 = 2
SP4
Set point 4 (in eng. units).
Range: from rL to rH.
SP4 is operative when logic input 1 and the logic
input 3 are closed and P50 = 2.
nnn
Software key for parameter protection.
This parameter is skipped if P18 = 0 or 1
On = the instrument is in LOCK condition
OFF = the instrument is in UNLOCK condition
OPERATIVE SET POINT SELECTION
It is possible to select the operating set point (SP, SP2,
SP3 or SP4) only by the binary conbination of the logic
inputs 1 and 3.
logic input 3
logic input 1
op. set point
open
open
SP
open
close
SP2
close
open
SP3
close
close
SP4
By setting the P50 parameter it is possible to limit the
number of the available set points.
SERIAL LINK
The device can be connected to a host computer by a
serial link.
The host can put the device in LOCAL (functions and
parameters are controlled via keyboard) or in REMOTE
(functions and parameters are controlled via serial link)
mode.
The REMOTE status is signalled by a LED labelled REM.
This instrument allows to modify the operative and
configuration parameters, via serial link.
The necessary conditions to implement this function are
the following:
1) Serial parameters from SEr1 to SEr4 should be
properly configurated.
2) Device must be in the OPERATING mode
During the downloading of configuration the device
goes in open loop with all output in OFF state.
At the end of configuration procedure, the device performs
an automatic reset and then returns to close loop control.
NOTE: from serial link it is not possible to perform the
"Feedback potentiometer calibration" as well as the action
performed by logic input 2 (Cnt 2).