Form 43343330
Aug 2012

-33-

4.

Check the burner at step pressure, observing burner ignition and flame characteristics. The burner should

ignite properly and without flashback to the orifice, and should remain lit.

GAS PRESSURE TABLE

GAS PRESSURE TABLE

GAS PRESSURE TABLE

GAS PRESSURE TABLE

GAS TYPE

GAS TYPE

GAS TYPE

GAS TYPE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

MANIFOLD PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

SUPPLY PRESSURE

Minimum*

Minimum*

Minimum*

Minimum*

Maximum

Maximum

Maximum

Maximum

Natural Gas

3.5” W.C.

5” W.C.

1

14” W.C.

Propane Gas

10.0” W.C.

11” W.C.

2

14” W.C.

* Minimum permissible gas supply pressure for purpose of input adjustment.

1

7” W.C. for Models 150-200

2

12” W.C. for Model 200

15.0)

ELECTRICAL CONNECTIONS

Failure to do so may result in death or serious injury.

This appliance must be connected to a properly grounded electrical source.

Disconnect electrical power and gas supply before servicing.

ELECTRIC SHOCK HAZARD

1.

All electric wiring shall conform to the latest edition of the National Electrical Code (ANSI/NFPA No. 70), or

the code legally authorized in the locality where the installation is made.

2.

The unit must be electrically grounded in accordance with the National Electrical Code (ANSI/NFPA No.

70-latest edition). In Canada, refer to current standard C22.1 Canadian Electrical Code Part 1.

3.

The wiring providing power to the heater shall be connected to a permanently live electrical circuit, one that

is not controlled by a light switch.

4.

The power supply to the unit should be protected with a fused disconnect switch or circuit breaker. A service

switch, as required by local codes, shall be located in the vicinity of the heater (check local codes for
allowable distances) and should be identified as Heater Service Switch. All electrical wiring must be located
in accordance with the required Clearances to Combustibles from the heater as listed on the nameplate on
the heater.

5.

Connection to the power supply is provided by an 18/3 gauge x 72” long cord with grounded 3 prong plug.

6.

The post purge function of the burner (fan on for 30 seconds after the call for heat) will only be enabled

when using a 24 Volt thermostat. With the line Voltage thermostat post purge operation is disabled.

Optional 24V thermostat connection

Jumper wire with 1/4” terminals pre-
installed. Remove the jumper and use
these two terminals for the 24V
thermostat connection if required.

72” grounded 3 prong
electrical cord

Liquid tight fitting
must be tight to
prevent ingress of
moisture in harsh
environments.