beautypg.com

Space Ray PTS Series Single Stage User Manual

Page 26

background image

Form 43343330
Aug 2012

-25-

12.0)

ATTACHING BURNER SCREEN – (200M BTU MODELS ONLY)

A burner screen is packaged with the control unit to prevent damage during shipment. This must be field
installed as shown below before operation of the heater.

1

2

3

4

1.

Remove cover panel 1.

2.

Remove screw securing burner casting to the gas manifold.

3.

Disconnect spark lead and sensing wire.

4.

Pull burner forward from the gas manifold and then out through the side of the box as shown.

5

Screen Tab

5.

Slide screen over burner until the tab stops against the rear of the burner cup.

6.

Check that the spark gas is 1/8” between the electrode and the burner casting as shown.

7.

Check that the flame sensor is aligned as shown.

8.

Re-install the burner assembly in reverse order.

1/8” spark gap

6

7

Burner
Screen

4-3/16”
ref.

This manual is related to the following products: