Seaward Supernova XE User Manual
Page 32

How to perform Automatic Tests
22
Review Test Results
Display the results from the test in tabular form:-
APPLIANCE :
A1212654673891
SITE
USER
: KITCHEN
: BOB
TESTCODE1 :
1027353823
TESTCODE 2
: 312169743A
TEST OUTPUT
LIMIT
RESULT
STATUS
EARTH BOND
25A
0.1ohms
0.99
PASS
EARTH BOND
25A
0.1ohms
0.98
PASS
INSULATION 500V 2Mohms
20.67 PASS
SUB LEAKAGE
7.5mA
<0.25
PASS
LOAD
2.00kVa
A fast key may illuminate to ‘view comments’.
Use the Red button to return to the previous menu.
Download Test Results
This option allows previous test results to be downloaded to either a
printer or a computer. The printer option allows a pass/fail label to be
printed on a compatible printer - see Chapter 6.
Main Menu
Return to the Main Menu.
Write Data to Smart Tag
This option can only be used when combined with the Seaward
Braincell/Smart Tag reader. Full details of this option can be found in
the manual which is supplied with every Braincell/Smart Tag reader.
Abort Actions
During an Automatic test, pressing the Red Button immediately stops