FOR THE PLUMBER

CONFORM TO ALL APPLICABLE CODES

Water Supply:
The recommended water supply line is 3/8" O.D.
copper tubing, with a minimum operation pressure
of 20 PSIG, and a maximum of 120 PSIG.
Connect to cold water using the male flare
connection at the back of the machine. Install a
shut off valve in an accessible space between the
ice maker and the water supply.

Drain System:
All drains are of the gravity type, and must have a
minimum of 1/4" fall per foot of horizontal run. The
drains must be installed to conform to local
plumbing codes. The use of a vent at the machine
and at the bin will allow the system to drain
properly. Use only rigid tubing for drains; insulation
of the bin drain is recommended.

SHUT OFF

VALVE

FIELD

SUPPLIED

WATER FILTER

3/8" MALE FLARE

3/4" FPT

VENT THIS DRAIN

WATER INLET

BIN DRAIN

FLOOR DRAIN

FM2400RH