Service Diagnosis:

SYMPTOM

POSSIBLE CAUSE

PROBABLE FIX

No ice is made, nothing operates

Unit off, due to no power

Restore power

Unit off, due to master switch in
OFF position

Switch master switch to ON

Unit off, due to bin thermostat
open

Check temperature at bin
thermostat bracket, if warmer
than 40

o

F., thermostat should be

closed. Adjust/replace thermostat.

Unit off, due to hi pressure cut out
open

Reset and check for dirty
condenser, hot location, or water
interruption (if water cooled).

Unit off, due to hi temperature cut
out open

Hot gas valve leaking thru,
replace hot gas valve.

Unit off, due to circuit board open

Check for short circuit and
replace circuit board.

No ice is made

No water due to water turned off.

Reconnect water supply

No water due to water filter
plugged.

Replace water filter

No water due to inlet water valve
screen plugged

Clean out inlet screen

No water due to strainer screen
plugged

Clean out inlet screen

No water due to Inlet water valve
coil open

Replace valve

No water due to inlet water valve
will not open

Replace valve

Water in reservoir, but no water
over evaporators

Water pump does not work,
replace pump

No cooling at evaporator due to
compressor switched off

Switch compressor on.

No cooling at evaporator due to
too much heat load because inlet
water valve leaks thru

Replace inlet water valve

No cooling at evaporator due to
hot gas valve leaking thru

Replace hot gas valve

No cooling at evaporator due to
fan not turning

Check & replace fan motor or fan
control switch

No cooling at evaporator due to
dirty condenser

Clean condenser