RLE TSP User Manual
Page 4
Installation & Operations
Remote Probe Transmitters and Remote Sensor Transmitters
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specifications subject to change without notice.
BA/#-(PP, RPP, RPFEP) Temperature Sensor
20921_ins_RemoteSen_Active
rev. 04/18/13
BA/FPB-50 Flexible probe brackets (50 units)
BA/Foamback White foam insulation 2.6” x 4.4” x 0.25 thick
4 of 4
Sensitivity: Approximate @ 32ºF (0ºC)
Thermistor:
Non-linier - (See www.bapihvac.com,
click “Sensor Specs”)
RTD (Pt):
3.85Ω/ºC for 1KΩ RTD
0.385Ω/ºC for 100Ω RTD
Lead wire
22awg stranded
Wire Insulation
-PP
Etched Teflon leads, plenum rated
-RPP
Flame Retardant PVC plenum cable
-RPFEP
FEP jacketed plenum rated cable
-RPFEP2
FEP jacketed plenum and
submersion rated cable
Probe
-PP
Heat conductive plastic cup
-RPP, RPFEP
Rigid, 304 Stainless Steel, 0.25” OD
Probe Length
-PP
0.875” (22.2mm)
-RPP, RPFEP
1.75” (44.5mm)
Mounting
External Probe Bracket required
Probe
Vented polycarbonate shield, ½” OD
Probe Length
1.2” with ½” NPT threads
Mounting
Extension tabs (ears), 3/16” holes
Wall Gasket
Closed cell foam (impervious to mold)
Enclosure Types
Weather Proof
-WP, w/ two ½” FNPT entries, (Bell box)
BAPI-Box
-BB, w/ four ½” NPSM & one ½” drill-outs
BAPI-Box 2
-BB2, w/ three ½” NPSM & three ½” drill-outs
Weather Tight
-EU, -EUO, w/ two ½” knock-outs
Enclosure ratings
Weather Proof
-WP, NEMA 3R, IP14
BAPI-Box
-BB, NEMA 4, IP66
BAPI-Box 2
-BB2, NEMA 4, IP66
Weather Tight
-
EU, NEMA 4, IP66, UV rated
Enclosure materials
Weather Proof
-WP, Cast Aluminum, UV rated
BAPI-Box
-BB, Polycarbonate, UL94V-0, UV rated
BAPI-Box 2
-BB2, Polycarbonate, UL94V-0, UV rated
Weather Tight
-EU, ABS Plastic, UL94V-0, UV rated
Ambient (Enclosure): 0 to 100% RH, Non-condensing
BB, BB2
-40ºF to 185ºF, (-40º to 85ºC)
EU & EUO
-40ºF to 185ºF, (-40º to 85ºC)
WP
-40ºF to 212ºF, (-40º to 100ºC)
Agency
RoHS, CE (CE for all sensors below 10KΩ)
PT = DIN43760, IEC Pub 751-1983,
JIS C1604-1989
Specifications
Related Products
RTD Transmitter
Power Required:
7 to 40VDC
Transmitter Output: 4 to 20mA, 850Ω@24VDC
Output Wiring:
2 wire loop
Output Limits:
<1mA (short), <22.35mA (open)
Span:
Min. 30ºF (17ºC), Max 1000ºF, (555ºC)
Zero:
Min. -148°F (-100°C), Max 900ºF (482ºC)
Zero & Span Adjust: 10% of span
Accuracy:
±0.065% of span
Linearity:
±0.125% of span
Power Output Shift: ±0.009% of span
RTD Sensor:
2 wire Platinum (Pt), 385 curve
Transmitter Ambient -4 to 158ºF(-20 to 70ºC)
0 to 95% RH, Non-condensing
Thermistor Transmitter
Supply Voltage:
10 to 35 VDC (0 to 5 VDC or 4 to 20 mA Outputs)
15 to 35 VDC (0 to 10 VDC Output)
12 to 24 VAC (0 to 5 VDC Outputs)
15 to 24 VAC (0 to 10 VDC Output)
Transmitter Output: 4 to 20mA, 700Ω@24VDC
0 to 5 & 0 to 10VDC, 10KΩ min
Output Wiring:
2 & 3 wire (See wiring detail on pg. 3)
Transmitter Limits: -40 to 185ºF, (-40 to 85ºC)
Accuracy:
±1.015ºC, from (0 to 65ºC)
Linearity:
±0.065ºC, from (0 to 65ºC)
Resolution:
Span/1024
Thermistor Sensor: 10K-2 Thermistor, 10KΩ @77ºF
Transmitter Ambient: 32 to 158ºF, (0º to 70ºC)
0 to 95% RH, Noncondensing
Thermistor:
10K-2
,Thermal Resistor (Bare Sensor)
Accuracy (Std):
±0.36ºF, (±0.2ºC)
Accuracy (High):
±0.18ºF, (±0.1ºC),
[XP] option
Stability:
< 0.036ºF/Year, (<0.02ºC/Year)
Heat Dissipation:
2.7 mW/ºC
Probe Range:
-40º to 221ºF (-40º to 105ºC)
Wire Colors:
Standard:
Yellow/Yellow (no polarity)
High Acc. [XP]:
Yellow/Yellow (no polarity)
RTD:
Resistance Temp Device (Bare Sensor)
Platinum (Pt):
100Ω and 1KΩ @0ºC, 385 curve,
Pt Accuracy (Std): 0.12% @Ref, or ±0.55ºF, (±0.3ºC)
Pt Accuracy (High): 0.06% @Ref, or ±0.277ºF,
(±0.15ºC),
[A]option
Pt Stability:
±0.25ºF, (±0.14ºC)
Pt Self Heating:
0.4 ºC/mW @0ºC
Pt Probe Range:
-40º to 221ºF, (-40 to 105ºC)
Wire Colors:
General color code (other colors possible)
1KΩ, Class B
Orange/Orange (no polarity)
1KΩ, Class A
Orange/White (no polarity)
100Ω, Class B
Red/Red (no polarity)
100Ω, Class A
Red/Red-w/black stripe (no polarity)