The SD-RO1 is a single zone spot detector with one generic relay output. It can

be used in conjunction with any product that accepts a digital dry contact input.

The SD-RO1 requires an isolated power supply, either RLE part number

PSWA-DC-24 or WA-AC-24-ST. These power supplies are sold separately and are

available from RLE.

If the SD-RO1 is operating on 24VAC power, the circuit will reset and open

automatically once a detected leak is no longer present. If the SD-RO1 is

operating on 24VDC power, the circuit must be manually reset after a leak is

detected and cleared. To do this, you must break power to the device, which

will reset the circuit. Even if the water leak is no longer present, power must be

broken to manually reset the DC-powered SD. The easiest way to accomplish

this manual reset is to install a reset switch on either the positive or negative

wire of the power supply that feeds into the SD-RO1.

To connect the SD-RO1 to a controller:

1. Connect the white (N/O) and green (Common) or blue (N/C) leads to the

alarm device.

2. Connect the black (-) and red (+) leads to the power source.

If the SD-Z is being added to an existing system - connected in a chain with

other SD-Z devices or cable - undo the appropriate coupling, insert the SD-Z into

the chain, and secure all connections.

SD-Z

Designed to work with either zone or distance-read leak detection controllers,

the SD-Z can also be connected to other SD-Z units or to sensing or non-sensing

cable. When used with a distance-read system, the SD-Z simulates 50 feet of

cable - 25ft. (7.62m) from the male connector to the SD-Z, and 25ft. (7.62m)

from the SD-Z to the female connector.

Because a SD-Z cannot connect directly to a controller, leader cable and an EOL

terminator are required for installation. RLE packages these components as

an LC kit. If you’re adding the SD-Z to an existing RLE leak detection system,

additional leader cable and EOL may be unnecessary. Please check your supplies

before you attempt to install the SD-Z.

When you connect RLE leak detection components, the male pins in the

connectors should always point toward the controller. Therefore, connect the

black connector with the pins to the control head, and place the EOL on the

connector without pins.