REMKO PG 12 User Manual

Page 9

background image

9

– unit doesn’t start

– unit stops during operation

– fan blows, but gas supply is blocked

resp. no ignition

– flame goes out after having released the pin of

thermoelectric gas valve

– gas supply is blocked, resp. flame goes out

– fuel consumption is too high

– unit can’t be shut down

– heating capacity drops during continuous operation

1 – 2 – 3 – 4 – 7

2 – 4 – 7 – 12 – 13

4 – 5 – 8 – 9 – 12

8 – 10 – 11

4 – 6 – 7 –10 – 11 – 12 – 13

12 – 15

3 – 14

13

,

-

& . %!

cause:

trouble:

Make sure that the gas supply has been closed and the mains plug has been taken out of the mains

socket before carrying out any work regarding the unit!

Setting and maintenance is to be carried out by authorized experts only!

cause:

remedy:

1. no electrical connection

-

plug the mains into an appropriate mains socket (230V/1~ 50Hz)

2. fan motor is overcharged

(fan blows irregularly or is blocked)

-

check fan motor, fan blade and clutch plate and replace if necessa-

ry.

3. operating switch defect

-

close gas supply, unplug the mains and replace defect operating

switch

4. no gas pressure on solenoid valve

-

check gas supply

-

check contents of gas cylinders

-

check gas hose(s) for damage

-

release hose break protection resp. replace it

5. no ignition spark

-

set ignition electrode

-

check ignition cable

-

check porcelain insulation of ignition electrode

6. air-suction grille impurified

-

clean air-suction grille

7. unit is shut down by safety thermostat (STB)

-

check air-suction and blow-out grille and clean if necessary

-

check fresh air supply

-

release safety thermostat (STB - Reset)

8. safety pilot does not open (resp. does not lock)

-

replace safety pilot

9. piezo igniter defect

-

replace piezo igniter

10. thermocouple resp. temperature limiter defect

-

check position of thermocouple and adjust according to setting hints

11. loose or impurified connection between safety pilot and termo-

couple

-

check connection and clean if necessary

12. pressure controller defect or false pressure controller mounted

resp. hose break protection is blocked

-

mount original pressure controller

-

release hose break protection resp. replace it

13 gas cylinder(s) iced over due to low temperatures and too high

gastaking

-

replace empty gas cylinder(s) and connect 2-3 cylinders using multi

cylinder set (EDV-No. 1014050)

14. solenoid valve does not open

-

close gas supply

-

let flame burn out

-

put operating switch in position „0” and unplug the mains

-

replace solenoid valve

15. leak gas hose(s)

-

find leakage by foam forming mediums eleminate leakage