Please observe the following:

We recommend that the customer install a main or

repair switch close to the outdoor unit.

Power is supplied to the indoor unit via a control line

from the outdoor unit.

The system’s fuse protection must comply with the

technical data.

The electrical terminals of the connections are lo-

cated on the lower right hand side of the indoor unit.

Condensation Connection


Condensation forms on the plate fin exchanger of the
indoor unit during cooling operation because tempera-
tures below the dew point are reached.
The indoor unit is equipped with a collection tray and a
condensation hose for the condensation that accumu-
lates.
Follow the instructions below to lay the condensation
hose:

The condensation drainage pipe is generally placed

in the same guideway as the refrigerant pipes.

If, as a result of structural design conditions, it is neces-

sary to have a different guideway for the condensation
hose, the hose can also be guided to the indoor unit
through a different drain.

If the unit is being operated at outside temperatures be-

low 0°C, the pipes must be placed in such a way that
they are protected from frost.

Always use suitable hose clips.
If the condensation is being guided to a drainage

pipe, please install a siphon-like hose guideway.
which acts as an odour seal.

Outdoor unit

Reversing valve

Power supply

Indoor unit

L

N

7

L1

N

L

N

7

8 8

Control conductor

230 V~,
50 Hz,
L1 / N / PE

Fan motor

9

9

PE PE

PE

Connection of outdoor units RKS 526 H to 568 H
Cooling and heating mode

Wiring Diagram

Terminal

Cover

Strain relief

Control line

Control line

Connection of outdoor units RKM 610 to 813
Cooling mode

Outdoor unit

Compressor contactor

Power supply

Indoor unit

A

N

2

L1

N

L

N

PE PE

PE

Control conductor

neutral conductor

phase conductor

230 V~,
50 Hz,
L1 / N / PE

Connection of outdoor units RKS 526 to 568
Cooling mode

Outdoor unit

Compressor contactor

Protecting earthing
conductor

Power supply

Indoor unit

L

N

7

L1

N

L

N

PE PE

PE

Control conductor

neutral conductor

phase conductor

230 V~,
50 Hz,
L1 / N / PE

To connect the units, proceed as follows:

1. Open the air inlet grille.
2. Using a Phillips screwdriver, loosen the cover on the

right side.

3. Connect the unit to the current-free line from the

outer unit.

See Wiring Diagram.

4. Reassemble the unit.

2% incline

Make sure there is an adequate

incline for drainage.
It must be at least 2 %!

The supplied condensation

hose can be extended using
standard hoses.

Since condensation is created, the condensation

pipe must be isolated.

After the hose has been laid, check to make sure

that condensation can drain freely.

Protecting earthing