Remko pwl – REMKO PWL 101 HK User Manual
Page 18
18
REMKO PWL
Type
PWL 301-H
PWL 302-H
PWL 303-H
Type
2-speed
2-speed
2-speed
Speed
rpm
920
750
920
750
920
750
Electrical connection
400/3~N
Frequency
Hz
50
Power consumption
kW
0.36/0.22
Nominal current
A
0.84/0.46
Air capacity
m³/h
4300
2650
4150
2400
3900
1710
Sound pressure level
1)
dB (A)
66
59
66
59
68
61
max. mounting height
m
7.0
6.5
6.0
max. range
2)
m
5.0
7.0
6.2
Hydraulic connection
Inch
R 1“
R 1“
R 1“
Water volume
l
1.1
2.0
3.3
Weight
kg
43
46
48
PWW heating
medium
t
L1
°C
kW
t
L2
°C
kW
t
L2
°C
kW
t
L2
°C
kW
t
L2
°C
kW
t
L2
°C
kW
t
L2
°C
50 / 40 °C
0
14.7
21
11.1
12
24.0
16
17.2
20
33.7
24
19.1
31
5
12.8
13
9.6
15
20.8
19
15.0
23
29.6
26
16.8
33
10
10.9
17
8.2
19
17.7
22
12.8
25
25.5
29
14.5
34
15
9.0
21
6.8
23
14.7
25
10.6
28
21.5
31
12.2
36
20
7.1
25
5.4
28
11.7
28
8.5
31
17.6
33
10.0
37
60 / 50 °C
0
18.7
12
14.0
15
30.4
20
21.7
25
41.7
30
23.6
38
5
16.7
16
12.5
18
27.1
23
19.4
28
37.5
32
21.2
40
10
14.7
20
11.1
22
24.0
27
17.1
31
33.3
35
18.8
42
15
12.8
24
9.6
26
20.9
30
14.9
33
29.2
37
16.5
43
20
10.9
28
8.2
29
17.8
33
12.8
36
25.2
39
14.3
45
70 / 50 °C
0
18.8
12
14.3
15
31.0
21
22.3
26
44.8
32
25.6
41
5
16.9
16
12.7
19
27.8
24
20.0
29
40.5
34
23.2
43
10
14.9
20
11.3
22
24.6
27
17.8
31
36.3
37
20.8
45
15
13.0
24
9.8
26
21.5
30
15.6
34
32.1
39
18.4
46
20
11.1
28
8.4
29
18.5
33
13.4
37
28.1
41
16.1
48
80 / 60 °C
0
22.9
15
17.2
18
37.5
25
26.9
31
52.9
38
30.1
49
5
20.9
19
15.7
22
34.2
28
24.6
34
48.6
40
27.6
51
10
18.9
23
14.2
25
31.0
31
22.3
37
44.3
43
25.2
52
15
16.9
27
12.8
29
27.8
35
20.0
39
40.1
45
22.8
54
20
15.0
30
11.3
33
24.7
38
17.8
42
35.9
47
20.5
56
90 / 70 °C
0
26.9
17
20.3
21
44.0
29
31.5
36
61.1
43
34.7
56
5
24.9
21
18.7
25
40.7
33
29.1
39
56.6
46
32.1
58
10
22.9
25
17.2
29
37.4
36
26.8
42
52.3
48
29.6
60
15
20.9
29
15.7
32
34.2
39
24.5
45
48.0
51
27.2
61
20
18.9
33
14.0
36
31.0
42
22.2
48
43.8
53
24.8
63
We reserve the right to make dimensional and design changes in the interest of technical advances.
PWL 301-303 - Heating • Rating tables • Technical Data
t
L1
= air inlet temperature/t
L2
= air outlet temperature
2)
at
∆
t 20 K (difference in temperature between air inlet and air outlet)
Operation with range restriction