Repair – REMKO PWL 101 HK User Manual

Page 11

background image

11

ATTENTION

After carrying out all work on
the units, an electrical safety
test must be carried out in
accordance with VDE 0701.

NOTE

Only authorised specialists
may undertake repairs and
maintenance.

Repair

If the fin exchanger surface is

covered with grease or sooty
particles, the exchanger ele-
ment can be removed and
cleaned with a steam-jet degre-
aser using low pressure and a
suitable cleaning agent.

Remove heavy fouling on the

fan and aluminium fins with a
soap solution.

Clean the condensate tank in

the unit housing to remove dirt
deposits.

To ensure complete drainage of
the condensate tank, the suction
opening of the condensate hose
must be fixed at the lowest point
of the cover.
The condensate sensor must be
arranged slightly above the suction
opening.

Bottom edge of sensor = top edge
of suction opening.

Routing must take place as show
in the following diagram.
F = Sensor cable
K = Condensate hose (internal ø 6)

F

K

Replacing the fin heat exchanger

1. Remove the cover of the unit

completely.
(See care and maintenance)

2. Disconnect the electrical con-

nection of the fan.

3. Disconnect the hydraulic con-

nection.

4. Remove the bottom support

plate (6 screws).

5. Remove the support plate with

fin exchanger downwards.

6. Carefully re-install the replace-

ment heat exchanger and all
further components in reverse
order.

Fan replacement

1. Remove the cover of the unit.

(See care and maintenance)

2. Disconnect the electrical con-

nection of the fan.

3. Remove the protection grille

with fan from the housing.

4. Carefully refit the new fan in

reverse order.

5. Check the fan impeller for

smooth operation and freedom
of movement with respect to
the fan housing.

6. Re-establish the electrical con-

nection of the motor correctly.

ATTENTION

Prior to carrying out mainte-
nance or repairs, the unit must
always be disconnected from
the mains supply and locked to
prevent unauthorised recon-
nection.

Recommended maintenance interval in normal unit operation

Inspection and possible cleaning of the condensate tank

Every six months

Inspection and possible cleaning of the condensate drain

Every six months

Functional check of the condensate pump and alarm sensor

Every six months

Inspection and possible cleaning of the air grille

Annually

Inspection of the electrical connections and earthing

Annually

Cleaning of the fin exchanger

Annually

Inspection of the fan for smooth operation and function

Annually