beautypg.com

Introduction – Pennco 3KW0.60 User Manual

Page 3

background image

3

Boiler is a natural draft oil fired hot water boiler comprised

of cast iron sections. Boiler is available with 3, 4, or 5 cast

iron sections. Sections are held together by cast iron push

nipples.

Boiler is capable of firing #2 fuel oil from 0.60 gph

up to 2.00 gph. All packaged boilers include, limit,

temperature and pressure gauge, safety relief valve,

drain valve, flue brush, and an extra boiler tapping for
expansion tank or air elimination.

OIL-FIRED HOT WATER BOILERS

RATINGS & CAPACITIES

BOILER

MODEL

No.

of

Sections

Firing

Rate

†GPH

Input

**MBH

***

Heating

Capacity

**MBH

Net

AHRI

Rating

**MBH

Minimum

Chimney

Size/Height

A.F.U.E.

††

Dimensions (Inches)

A

B

C

3KW0.60

3

0.60

84

74

64

8”x8”x15’

86.1*

17 3/4

6

9 3/4

3KW0.75

3

0.75

105

92

80

8”x8”x15’

85.6*

17 3/4

6

9 3/4

3KW1.00

3

1.00

140

120

104

8”x8”x15’

84.4

17 3/4

6

9 3/4

4KW.90

4

0.90

126

111

97

8”x8”x15’

86.0*

21

6

11 3/8

4KW1.25

4

1.25

175

153

133

8”x8”x15’

85.9*

21

6

11 3/8

4KW1.50

4

1.50

210

181

157

8”x8”x15’

85.1*

21

6

11 3/8

5KW1.20

5

1.20

168

147

128

8”x8”x15’

86.1*

24 1/4

6

13

5KW1.75

5

1.75

245

210

183

8”x8”x15’

85.0*

24 1/4

6

13

5KW2.00

5

2.00

280

239

208

8”x8”x20’

84.0

24 1/4

6

13

• These firing rates available only with alternate firing rate kits.

** MBH = 1,000 Btu Per Hour BTU = British Thermal Unit

*** Heating capacity based on 13% CO2 with 0.02” W.C. draft over fire, and #1 smoke or less. Testing was done

in accordance with D.O.E. (Department Of Energy) test procedure.

† GPH = Gallons Per Hour Of Oil At 140,000 Btu Per Gallon

†† A.F.U.E. = Annual fuel utilization efficiency based upon D.O.E. Test procedure.

* As Energy Star Partner, manufacturer has determined this product meets Energy Star guidelines for energy

efficiency.

Net AHRI Water Ratings based on piping allowance of 1.15. Consult manufacturer before selecting a boiler for

installations having unusual piping and pickup requirements, such as intermittent system operation, extensive

piping systems, etc.

INTRODUCTION

BOILER RATINGS AND CAPACITIES

Figure 1 - Dimensions

This manual is related to the following products: